Statutory compliance

Fire safety compliance

Under the Regulatory Reform (Fire Safety) Order 2005, the responsible person for a non-domestic building must keep a suitable fire risk assessment and maintain fire safety systems. In practice that means weekly fire alarm tests, monthly emergency lighting checks and an annual full-duration emergency lighting test, following BS 5839-1 and BS 5266-1.

The law behind it

  • Regulatory Reform (Fire Safety) Order 2005
  • Fire Safety (England) Regulations 2022 (additional duties for multi-occupied residential buildings)
  • BS 5839-1 (fire detection and alarm systems) and BS 5266-1 (emergency lighting)

What is due and when

CheckFrequency
Fire risk assessmentKept up to date and reviewed regularly, and after any significant change
Fire alarm call-point testWeekly
Fire alarm service by a competent personAt least every six months (BS 5839-1)
Emergency lighting function testMonthly (BS 5266-1)
Emergency lighting full-duration testAnnually (BS 5266-1)
Fire extinguisher serviceAnnually (BS 5306-3)

The duty sits with the responsible person — usually the employer, owner or managing agent — even when the testing is contracted out.

Records matter as much as the tests: an enforcing authority will ask to see the log book.

Official source: GOV.UK — Fire safety in the workplace. This page summarises the guidance; it is not legal advice.