Fire safety compliance
Under the Regulatory Reform (Fire Safety) Order 2005, the responsible person for a non-domestic building must keep a suitable fire risk assessment and maintain fire safety systems. In practice that means weekly fire alarm tests, monthly emergency lighting checks and an annual full-duration emergency lighting test, following BS 5839-1 and BS 5266-1.
The law behind it
- Regulatory Reform (Fire Safety) Order 2005
- Fire Safety (England) Regulations 2022 (additional duties for multi-occupied residential buildings)
- BS 5839-1 (fire detection and alarm systems) and BS 5266-1 (emergency lighting)
What is due and when
| Check | Frequency |
|---|---|
| Fire risk assessment | Kept up to date and reviewed regularly, and after any significant change |
| Fire alarm call-point test | Weekly |
| Fire alarm service by a competent person | At least every six months (BS 5839-1) |
| Emergency lighting function test | Monthly (BS 5266-1) |
| Emergency lighting full-duration test | Annually (BS 5266-1) |
| Fire extinguisher service | Annually (BS 5306-3) |
The duty sits with the responsible person — usually the employer, owner or managing agent — even when the testing is contracted out.
Records matter as much as the tests: an enforcing authority will ask to see the log book.
Official source: GOV.UK — Fire safety in the workplace. This page summarises the guidance; it is not legal advice.